Product Datasheet
IO-Link Safety Hub, 8 DI + 8 DO, 8× M12 (BNI IOL-355-S02-Z071)
Model: BNI00JF
| Category | IO-Link Masters and Hubs |
| Brand | Balluff |
| Model | BNI00JF |
| Datasheet PDF | https://r1ju38jd9x.ufs.sh/f/F5LGowJcoU060gNMioHEme34Vr9lb7E2WU8TcQBzfFp6uMZa |
IO-Link blocks for safety applications – BNI IOL-355-S02-Z071
Performance Level: to d
Safety category (EN ISO 13849-1): 3
SIL (IEC 61508): 2
SIL CL (EN 62061): 2
Response time max.: 6 ms
Approval/Conformity: CE, UKCA, Safety, cULus, WEEE
Current sum US, sensor: 1.2 A
Current sum UA, actuator: 16 A
Digital inputs: 8x PNP, Type 3
Digital outputs: 8x PNP
Interface: IO-Link 1.1
Connection slots: 8x M12x1-Female, 5-pin, A-coded
Technical specifications
| General | Model designation | BNI IOL-355-S02-Z071 |
| General | Approval/Conformity | CE, UKCA, Safety, cULus, WEEE |
| Electrical | Current sum US, sensor | 1.2 A |
| Electrical | Current sum UA, actuator | 16 A |
| Connection | Connection slots | 8x M12x1-Female, 5-pin, A-coded |
| Mechanical | Dimension | 68 x 31.7 x 181.5 mm |
| Mechanical | IP rating | IP67 |
| Mechanical | Housing material | Zinc, Die casting, nickel-plated |
| Environment | Ambient temperature | -5…55 °C |
| Safety | SIL (IEC 61508) | 2 |
| Safety | Performance Level | to d |
| Communication | Interface | IO-Link 1.1 |
| I/O | Digital inputs | 8x PNP, Type 3 |
| I/O | Digital outputs | 8x PNP |
InfiSense Technologies Co., Ltd.
Printed: 20 November 2026
Information may change — please check with our team.