← Back to product|Datasheet: Mef Emc-Filter 3-Phase 1-Stage With Neutral, I:6A U:4x440 VAC snap on 10511
Product Datasheet
Mef Emc-Filter 3-Phase 1-Stage With Neutral, I:6A U:4x440 VAC snap on
Model: 10511
| Category | EMC Filters |
| Brand | Murrelektronik |
| Model | 10511 |
Murrelektronik emc filter, model MEF 3/1 N 6A T (I:6A U:4x440 VAC snap on).
Features:
• Current: 6 A
• DIN-rail mountable
• with neutral
• Attenuation curves on request.
• The 3-phase and one-stage EMC filters MEF 3/1 are used in the range 0.1...30 MHz and dampen interferences found in cables from the mains, supply units and control systems. They are suitable for TN-S, TN-C-S, and TT networks. The best results are obtained with short connection cables (suggestion: earth connection < 10 cm) of the largest possible cross-section. The EMC filters are bi-directional. They reduce symmetrical and asymmetrical interferences that regularly appear with electronically controlled three phase units through mains influences.
Dimensions (W x H x D): 56 mm x 107 mm x 39 mm.
Technical specifications
| General | Weight | 0.326 kg |
| General | Country of origin | IT |
| General | Model designation | MEF 3/1 N 6A T |
| Technical data | Depth | 39 mm |
| Technical data | Width | 56 mm |
| Technical data | Gender | female |
| Technical data | Height | 107 mm |
| Technical data | Connection | Screw terminals SK |
| Technical data | No. of poles | 1 |
| Technical data | Mounting method | snap-on |
| Technical data | Power frequency | 50 ... 60 Hz |
| Technical data | Overload current | 18× (IN t) max. 0.5 ms; 1.5× (IN t) max. 1 min. (1× per hour) |
| Technical data | Phase number input | 3 |
| Technical data | Leakage current max. | 3 mA @ 250 V AC, 50 Hz |
| Technical data | AWG number solid max. | 9 |
| Technical data | AWG number solid min. | 24 |
| Technical data | Color contact carrier | green-yellow |
| Technical data | Family construction form | terminal |
| Technical data | Operating voltage AC max. | 440 V |
| Technical data | Suitable for mounting type | Mounting rail TH35, (EN 60715) |
| Technical data | Insulation test voltage L-L | 2.1 kV |
| Technical data | Insulation test voltage L-N | 2.7 kV |
| Technical data | Duration insulation test voltage | 2s |
| Technical data | Climatic category (EN IEC 60068-1) | 25/085/21 |
| Technical data | Connection cross-section solid max. | 6 mm² |
| Technical data | Connection cross-section solid min. | 0.2 mm² |
| Technical data | AWG number stranded/fine stranded max. | 11 |
| Technical data | AWG number stranded/fine stranded min. | 24 |