Skip to content
← Back to product|Datasheet: Mef Emc-Filter 3-Phase 1-Stage, I:25A U:3x600 VAC book-style 10533
Product Datasheet

Mef Emc-Filter 3-Phase 1-Stage, I:25A U:3x600 VAC book-style

Model: 10533

InfiSense Technologies
Mef Emc-Filter 3-Phase 1-Stage, I:25A U:3x600 VAC book-style
CategoryEMC Filters
BrandMurrelektronik
Model10533
Murrelektronik emc filter, model MEF 3/1 25A T (I:25A U:3x600 VAC book-style). Features: • Current: 25 A • 1-stage • Attenuation curves on request. • The MEF 3/1-3/2 3-phase and 1-/2-stage mains suppression filters are used in the 0.1...30 MHz range to suppress conducted interference on mains and supply lines. They are suitable for TN-C networks. The best filter effect is achieved with short connecting lines (recommendation: PE connection < 10 cm) with the largest possible cross sections. Line suppression filters act bidirectionally (in both directions). They reduce symmetrical and asymmetrical interference, which often occurs with frequency converters and switched-mode power supplies. Dimensions (W x H x D): 90 mm x 250 mm x 100 mm.

Technical specifications

General | Weight1.300 kg
General | Country of originIT
General | Model designationMEF 3/1 25A T
Technical data | Depth100 mm
Technical data | Width90 mm
Technical data | Genderfemale
Technical data | Height250 mm
Technical data | ConnectionScrew terminals SK
Technical data | No. of poles3
Technical data | Mounting methodscrewed
Technical data | Power frequency50 ... 60 Hz
Technical data | Overload current18× (IN t) max. 0.5 ms; 1.5× (IN t) max. 1 min. (1× per hour)
Technical data | Phase number input3
Technical data | Leakage current max.10 mA @ 250 V AC, 50 Hz
Technical data | AWG number solid max.7
Technical data | AWG number solid min.24
Technical data | Color contact carriergray
Technical data | Family construction formterminal
Technical data | Operating voltage AC max.600 V
Technical data | Insulation test voltage L-L3.1 kV
Technical data | Insulation test voltage L-N3.3 kV
Technical data | Duration insulation test voltage2s
Technical data | Climatic category (EN IEC 60068-1)25/085/21
Technical data | Connection cross-section solid max.10 mm²
Technical data | Connection cross-section solid min.0.2 mm²
Technical data | AWG number stranded/fine stranded max.9
Technical data | AWG number stranded/fine stranded min.24