Skip to content
← Back to product|Datasheet: Mef Emc-Filter 3-Phase 1-Stage With Neutral, I:135A U:4x500 VAC 10578
Product Datasheet

Mef Emc-Filter 3-Phase 1-Stage With Neutral, I:135A U:4x500 VAC

Model: 10578

InfiSense Technologies
Mef Emc-Filter 3-Phase 1-Stage With Neutral, I:135A U:4x500 VAC
CategoryEMC Filters
BrandMurrelektronik
Model10578
Murrelektronik emc filter, model MEF 3/1 N HD 135A T (I:135A U:4x500 VAC). Features: • Current: 135 A • with neutral • with increased damping • Attenuation curves on request. • The 3-phase and one-stage EMC filters MEF 3/1 are used in the range 0.1...30 MHz and dampen interferences found in cables from the mains, supply units and control systems. They are suitable for TN-S, TN-C-S, and TT networks. The best results are obtained with short connection cables (suggestion: earth connection < 10 cm) of the largest possible cross-section. The EMC filters are bi-directional. They reduce symmetrical and asymmetrical interferences that regularly appear with electronically controlled three phase units through mains influences. Dimensions (W x H x D): 180 mm x 170 mm x 140 mm.

Technical specifications

General | Weight4.500 kg
General | Country of originIT
General | Model designationMEF 3/1 N HD 135A T
Technical data | Depth140 mm
Technical data | Width180 mm
Technical data | Genderfemale
Technical data | Height170 mm
Technical data | ConnectionScrew terminals SK
Technical data | No. of poles4
Technical data | Mounting methodscrewed
Technical data | Power frequency50 ... 60 Hz
Technical data | Overload current18× (IN t) max. 0.5 ms; 1.5× (IN t) max. 1 min. (1× per hour)
Technical data | Phase number input3
Technical data | Leakage current max.15 mA @ 250 V AC, 50 Hz
Technical data | AWG number solid max.0
Technical data | AWG number solid min.5
Technical data | Color contact carriergray
Technical data | Family construction formterminal
Technical data | Operating voltage AC max.500 V
Technical data | Insulation test voltage L-L3.1 kV
Technical data | Insulation test voltage L-N3.3 kV
Technical data | Duration insulation test voltage2s
Technical data | Climatic category (EN IEC 60068-1)25/085/21
Technical data | Connection cross-section solid max.50 mm²
Technical data | Connection cross-section solid min.16 mm²
Technical data | AWG number stranded/fine stranded max.0
Technical data | AWG number stranded/fine stranded min.5