Murrelektronik safety relay, model MIRO SAFE+ T 2 24 (24 VAC/DC - 3 N/O contact / 2 N/O contact delayed). Features: • 6 A (STOP1); 8 A (STOP0) • Protection-door and emergency-stop control • Light curtain control • Safety magnetic switch control • Automatic/manual/manual monitored reset/start Dimensions (W x H x D): 45 mm x 100 mm x 121 mm. operating temperature -25 °C … 60 °C.

Technical specifications

General | Weight0.420 kg
General | Country of originDE
General | Model designationMIRO SAFE+ T 2 24
Technical data | Depth121 mm
Technical data | Width45 mm
Technical data | Genderfemale
Technical data | Height100 mm
Technical data | Derating45 °C
Technical data | ConnectionSpring clamp terminals FK
Technical data | No. of poles4
Technical data | Service life20 a
Technical data | Alarm outputs13-14, 23-24, 33-34
Technical data | Mounting methodsnap-on
Technical data | Input voltage AC24 V
Technical data | Input voltage DC24 V
Technical data | Material contactAg Sn O
Technical data | Switching current6A
Technical data | Auxiliary contacts31-32
Technical data | Condition lifetimeload-dependent
Technical data | Apparent power max.7,1 VA
Technical data | Electrical lifetime0 cycles
Technical data | Mechanical endurance0 cycles
Technical data | No. of alarm outputs3
Technical data | Color contact carrierblack
Technical data | Input voltage AC max.26,4 V
Technical data | Input voltage AC min.20,4 V
Technical data | Input voltage DC max.28,8 V
Technical data | Input voltage DC min.20,4 V
Technical data | Power consumption max.3,2 W
Technical data | Family construction formterminal
Technical data | Category (EN ISO 13849-1)4 (STOP0); 3 (STOP1)
Technical data | No. of auxiliary contacts1
Technical data | Switching voltage AC max.250 V
Technical data | Switching voltage DC max.250 V
Technical data | Operating temperature max.60 °C
Technical data | Operating temperature min.-25 °C
Technical data | Suitable for mounting type(EN 60715), mounting rail
Technical data | Material properties contactself-cleaning, positively driven
Technical data | DCavg STOP0 (EN ISO 13849-1)99 %
Technical data | Number of safety contacts STOP03
Technical data | SIL (EN/IEC 61508, EN IEC 62061)3 (STOP0); 2 (STOP1)
Technical data | DCavg STOP1 min. (EN ISO 13849-1)60 %
Technical data | Performance level (EN ISO 13849-1)e (STOP0); d (STOP1)
Technical data | Ambient temperature (storage, transport)-40 °C … 85 °C
Technical data | Switching capacity safety contacts STOP0max. 250 V AC/8 A; min. 10 V AC/10 mA (resist./ind.), at suitable suppression