Product Datasheet
Emparro ACCUcontrol UPS-Module, IN: 24VDC OUT: 24VDC/40A
Model: 85415
| Category | UPS and Buffer Modules |
| Brand | Murrelektronik |
| Model | 85415 |
Murrelektronik ups / buffer / redundancy module, model Emparro ACCUcontrol 40/24 (IN: 24VDC OUT: 24VDC/40A).
Features:
• INPUT: 24 V DC (SELV/PELV)
• OUTPUT: max. 40 A
Dimensions (W x H x D): 85 mm x 123 mm x 143 mm.
operating temperature -25 °C … 45 °C.
Technical specifications
| General | Weight | 0.751 kg |
| General | Country of origin | DE |
| General | Model designation | Emparro ACCUcontrol 40/24 |
| Technical data | Depth | 143 mm |
| Technical data | Width | 85 mm |
| Technical data | Gender | female |
| Technical data | Height | 123 mm |
| Technical data | Connection | Spring clamp terminals FK |
| Technical data | No. of poles | 6 |
| Technical data | Output current | 40 A |
| Technical data | Mounting method | snap-on |
| Technical data | Connection type 1 | X1 |
| Technical data | Connection type 2 | X2 |
| Technical data | Charging current max. | 2.5 A |
| Technical data | Color contact carrier | green |
| Technical data | Input voltage DC max. | 30 V |
| Technical data | Input voltage DC min. | 21.6 V |
| Technical data | Output voltage DC max. | 27.7 V |
| Technical data | Output voltage DC min. | 19.2 V |
| Technical data | Family construction form | terminal |
| Technical data | Output voltage adjustable | Yes |
| Technical data | Operating temperature max. | 45 °C |
| Technical data | Operating temperature min. | -25 °C |
| Technical data | Suitable for mounting type | (EN 60715), mounting rail TH35-7.5/TH35-15 |
| Technical data | Electric charge quantity max. | 40 Ah |