Illustration — the actual product may differ
Load Circuit ProtectionMico Pro electronic circuit protection, 4 channels, 2 A
Product code9000-41014-0200000
Mico Pro fix 4.2
- Type
- Electronic circuit protection
- Series
- MICO Pro
- Channels
- 4
- Current per channel
- 2 A
- Weight
- 0.141 kg
- Number of output channels
- 4
General
- Weight
- 0.141 kg
- Country of origin
- CZ
- Model designation
- Mico Pro fix 4.2
- Number of output channels
- 4
Electrical
- Total current max.
- 40 A
- Input voltage DC max.
- 30 V
- Input voltage DC min.
- 9V
- Switch-on capacity max.
- 30 mF
- Nominal input voltage DC
- 12 V … 24 V
- Trigger current per channel
- 2A
- Total current bridge set max.
- 40 A
- Trigger current tolerance max.
- 20 %
- Trigger current tolerance min.
- 0%
Connection
- Connection
- Bridge system
Mechanical
- Depth
- 114 mm
- Width
- 24 mm
- Height
- 130 mm
- Mounting
- Mounting rail TH35, (EN 60715)
- Degree of protection
- IP20
Environment
- Storage temperature
- -40 °C … 80 °C
- Operating temperature max.
- 55 °C
- Operating temperature min.
- -25 °C
Control
- System supply
- via power module
- Control options
- via power module
Mico Pro fix 4.2 · IN 24 V DC OUT 24 V DC / 2 A
- Electronic circuit protection, 4 channels, model Mico Pro fix 4.2
- 24 V DC
- Current per channel: 2 A
- Trips only the overloaded or short-circuited channel; other channels stay on
- DIN rail mounting (TH35)
How to order
- 1Send a quote requestList the product codes and quantities you need
- 2Receive the quotationOur team checks the request and sends you a quotation
- 3Delivery / installationConfirm the order, then we deliver or install on site