← Back to product|Datasheet: Switch-mode Power Supply PRO QL 240W 24V 10A, 24 V DC ± 1 % (3076370000) 3076370000
Product Datasheet
Switch-mode Power Supply PRO QL 240W 24V 10A, 24 V DC ± 1 % (3076370000)
Model: 3076370000
| Category | Power Supplies |
| Brand | Weidmüller |
| Model | 3076370000 |
Weidmüller PRO QL switch-mode power supply PRO QL 240W 24V 10A (order no. 3076370000). Power supply, switch-mode power supply unit, 24 V.
Power supply, switch-mode power supply unit, 24 V
Output 240 W 24 V DC ± 1 % ; rated input 100...240 V AC; efficiency 94.2 %; operating temperature -30 °C...70 °C; IP20.
Technical specifications
| General | Type | PRO QL 240W 24V 10A |
| General | Series | PRO QL |
| General data | MTBF | According to Standard: Telcordia SR-332 Operating time (hours), min.: 1,000,000 h Ambient temperature: 25 °C Input voltage: 230 V Output power: 240 W Duty cycle: 100 % |
| General data | Protection degree | IP20 |
| General data | Degree of efficiency | 94.2 % |
| General data | Short-circuit protection | Yes |
| General data | Mounting position, installation notice | Horizontal on DIN rail TS 35, top and bottom 50 mm clearance for free air flow, 10 mm clearance to neighbouring subassemblies. |
| Output | Output power | 240 W |
| Output | Connection system | Screw connection |
| Output | Output voltage, max. | 28 V |
| Output | Output voltage, min. | 24 V |
| Output | Output voltage, note | (adjustable via potentiometer) |
| Output | Rated output voltage | 24 V DC ± 1 % |
| Output | Residual ripple, breaking spikes | <150 mVPP |
| Connection data (input) | Connection system | Screw connection |
| Connection data (input) | Number of terminals | 3 for L/N/PE |
| Connection data (input) | Conductor cross-section, rigid , max. | 6 mm² |
| Connection data (input) | Conductor cross-section, rigid , min. | 0.34 mm² |
| Connection data (input) | Conductor cross-section, flexible , min. | 0.34 mm² |
| Connection data (input) | Conductor cross-section input (AWG), max. | 10 AWG |
| Connection data (input) | Conductor cross-section (AWG) (input), min. | 26 AWG |
| Connection data (output) | Connection system | Screw connection |
| Connection data (output) | Conductor cross-section, rigid , max. | 6 mm² |
| Connection data (output) | Conductor cross-section, rigid , min. | 0.34 mm² |
| Connection data (output) | Conductor cross-section, flexible , max. | 6 mm² |
| Connection data (output) | Conductor cross-section (AWG) (output), max. | 10 AWG |
| Connection data (output) | Conductor cross-section (AWG) (output) , min. | 26 AWG |
| Dimensions and weights | Depth | 111 mm |
| Dimensions and weights | Width | 48 mm |
| Dimensions and weights | Height | 125 mm |
| Dimensions and weights | Net weight | 761.17 g |
| EMC / shock / vibration | Interference immunity test acc. to | IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 3 GHz: 10 V/m IEC 61000-4-4 Fast transient/burst: DC/AC power port: ±4kV; data port: ±2kV; IEC 61000-4-5 Surge: Mains power port: ±2 kV (line-line), ±4 kV (line-earth); DC or Signal port:±0.5 kV (line-line), ±1 kV (line-earth) IEC 61000-4-6 CS: 10 V IEC 61000-4-8 IEC 61000-4-11 |
| EMC / shock / vibration | Vibration resistance IEC 60068-2-6 | 2.3 g |
| EMC / shock / vibration | Noise emission in accordance with EN55032 | Class B |
| Input | Inrush current | max. 40 A |
| Input | Connection system | Screw connection |
| Input | Frequency range AC | 47...63 Hz |
| Input | Rated input voltage | 100...240 V AC |
| Input | AC input voltage range | 100...240 V AC |
| Input | Recommended back-up fuse | 4 A / DI, safety fuse10 A, Char. B, circuit breaker3...4 A, Char. C, circuit breaker |
| Insulation coordination | Insulation voltage (input / earth) | 2 kV |
| Insulation coordination | Insulation voltage (input / output) | 3 kV |
| Insulation coordination | Insulation voltage (output / earth) | 0.5 kV |
| Temperatures | Storage temperature | -40 °C...85 °C |
| Temperatures | Operating temperature | -30 °C...70 °C |